Download Data Sheet
CONSTRUCTION & DIMENSIONS
-
CONDUCTOR PARAMETER
• Number of Conductors
3
• AWG Size
22
• Conductor Stranding
7x30
• Conductor Type
Bare copper
• Nominal DCR
17 Ohm/1000ft
INSULATION PARAMETER
• Insulation Type
Plenum PVC
• Insulation Thickness
0.007 in
• Insulation Color Code
1.Black,2.Red,3.White
SHIELDING PARAMETER
• Shield Type
Overall 100% Aluminum Foil
• Drain Wire Type
Tinned Copper
• Drain Wire AWG
24 AWG
ELECTRICAL CHARACTERISTICS
• Nom. Cap. Between Conductors
54 pF/ft
• Nom. Cap. Conductor to Shield
97 pF/ft
OVERALL CONSTRUCTION PARAMETERS
Jacket Type
Flexible Plenum
Jacket Thickness
0.015 in
Nominal Cable O.D.
0.13 in
Plenum
Yes
NEC UL Rating
CMP
RoHS Compliant
Pull Tension
30 lbs
Bend Radius
1.17 in
Cable Weight
18 lbs
Belden: 6501FE
OVERALL ELECTRICAL/OPTICAL CHARACTERISTICS
UL Flammability
NFPA 262 Plenum
Operating Range
-0 to 60 Deg C
UL Voltage Rating
300
RELATED PRODUCTS
Non Plenum Number
301
The Shopping Cart is currently empty